Pressure Switch Stuck Open On Goodman Furnace. If the inducer comes on the pressure switch is stuck closed. A disconnected or damaged pressure switch hose. Fixing this usually proves to be easy and inexpensive. So go ahead and put the hose back on put the access panel back on the furnace turn up the thermostat to its highest setting.
Jump to Latest Follow 21 - 32 of 32 Posts. Had service out yesterday to work on the furnace. Possible reasons your furnace pressure switch is stuck open include. Decipher two LED flashes to mean the draft blower is not working or your furnace has a short in the pressure switch circuit. If you have found that your pressure switch is not letting your furnace come on. It could be your pressure switch stuck open or closed.
I have taken the pressure switch off and blown on it reinstalled and no luck.
If the switch is open the inducer starts and the resulting pressure change closes the switch. The only way now for me to have heat is manual remove tube before start the unit and after its on a little bit plug it back on the inducer. So go ahead and put the hose back on put the access panel back on the furnace turn up the thermostat to its highest setting. An HVAC tech came over did a few measurements and found that the pressure switch right above the burner is not getting voltage so he opened up the circuit board unplugplug back the two wires connecting the switch and the board and then the furnace is back on until a couple of days ago same problem occurred. A disconnected or damaged pressure switch hose. I was having the same problem last year and replaced the pressure switch which fixed the problem but we are back to square one again.